Strany 1 - Operating Instructions

MAKING MODERN LIVING POSSIBLEOOperating InstructionsVLTp Soft Starter - MCD500

Strany 2 - MG.17.K3.02 - VLT

3.2 Dimensions and Weights177HA514.10MModel A mm(inches)B mm(inches)C mm(inches)D mm(inches)E mm(inches)Weight kg(lbs)MCD5-0021B295 (11.6) 278(

Strany 3 - 6 Operation

4 Electrical Installation4.1 Electrical Installation4.1.1 Control WiringThe soft starter can be controlled in three ways:••using the buttons on the LC

Strany 4 - 7 Programming

4.1.3 Remote InputsThe MCD 500 has three fixed inputs for remote control. These inputs should be controlled by contacts rated for low voltage, lowcurr

Strany 5 - 10 Specifications

4.1.6 Power TerminationsUse only copper stranded or solid conductors, rated for 75r C.NNOTESome units are aluminium bus bars. When connecting powerter

Strany 6 - 1 Safety

4.1.7 Motor ConnectionMCD 500 soft starters can be connected to the motor in-lineor inside delta (also called three-wire and six-wireconnection). The

Strany 7 - 2 Introduction

4.2.3 In-line Installation, Externally BypassedNon-bypassed models have dedicated bypass terminals, which allow the soft starter to continue providing

Strany 8 - 177HA382.11

4.3.1 Inside Delta Installation, Internally BypassedKM1 Main contactorF1 Fuses (optional)4.3.2 Inside Delta Installation, Non-bypassed177HA500.11M36/T

Strany 9 - 3 Installation

4.3.3 Inside Delta Installation, Externally BypassedNon-bypassed models have dedicated bypass terminals, which allow the MCD 500 to continue providing

Strany 10 - 177HA514.10

4.4.1 In-line Connection (Bypassed)NNOTEModels MCD5-0021B - MCD5-0215B are internally bypassed.Models MCD5-0245C - MCD5-1600C require an externalbypas

Strany 11 - 4 Electrical Installation

4.4.3 In-line Connection (Non-bypassed/Continuous) AAC-53a3-30:50-6AC-53a4-20:50-6AC-53a4.5-30:50-6MCD5-0245C 245 A 195 A 171 AMCD5-0360C 360 A 303 A

Strany 12 - 4.1.5 Earth Terminal

CContents1 Safety51.1 Safety52 Introduction62.1.1 Feature List 62.1.2 Type Code 73 Installation83.1 Mechanical Installation83.2 Dimensions and Weights

Strany 13 - 177HA542.11

4.4.5 Inside Delta Connection (Bypassed)NNOTEModels MCD5-0021B a MCD5-0215B are internally bypassed.Models MCD5-0245C a MCD5-1600C require an external

Strany 14 - 4.2 In-Line Installation

4.4.7 Inside Delta Connection (Non-bypassed/Continuous) AAC-53a3-30:50-6AC-53a4-20:50-6AC-53a4.5-30:50-6MCD5-0245C 368 A 293 A 257 AMCD5-0360C 540 A 4

Strany 15 - 177 HA4 31.11

4.5 Minimum and Maximum Current SettingsThe MCD 500's minimum and maximum full load current settings depend on the model: IIn-line Connection In

Strany 16 - 177HA500.11

CCAUTIONPower factor correction capacitors must be connected to theinput side of the soft starter. Connecting power factorcorrection capacitors to the

Strany 17 - 4.4 Current Ratings

4.10.2 Bussman Fuses - Square Body (170M)MModelSCR I2t (A2s)Supply Voltage(ื 440 VAC)Supply Voltage(ื 575 VAC)Supply Voltage(ื 690 VAC)MCD5-0021B 1150

Strany 18

* Two parallel connected fuses required per phase.4.10.4 Ferraz Fuses - HSJMModelSCR I2t (A2s)Supply Voltage(< 440 VAC)Supply Voltage(< 575 VAC)

Strany 19 - Starts Per Hour

4.10.5 Ferraz Fuses - North American Style (PSC 690)MModelSCR I2t (A2s)Supply Voltage< 440 VACSupply Voltage< 575 VACSupply Voltage< 690 VACM

Strany 20

4.10.6 UL Tested Fuses - Short Circuit RatingsMModel Nominal Rating (A) Short Circuit Rating 480V AC (kA) Short Circuit Rating 600V AC (kA) Fuse Ferra

Strany 21

4.11 Schematic Diagrams4.11.1 Internally Bypassed Models22216/T32/T113144/T2243334060508071718251116A6A5A45/L33/L215E1/L1+ 24 VDC + 542A31177HA425.101

Strany 22 - 4.9 Power Factor Correction

4.11.2 Non-bypassed Models177HA426.11E6/T32/T14/T25/L33/L21/L1L3BL2BL1B222113***14243334060508071718251116A6A5A415+ + 542A3124 VDC 11Control supply (m

Strany 23 - 4.10.1 Power Supply Fuses

4.9 Power Factor Correction214.10 Fuses224.10.2 Bussman Fuses - Square Body (170M) 234.10.3 Bussman Fuses - British Style (BS88) 234.10.4 Ferraz Fuses

Strany 24

5 Application Examples5.1 Motor Overload ProtectionThe thermal model used for motor overload in the MCD 500has two components:••Motor windings: These

Strany 25 - 4.10.4 Ferraz Fuses - HSJ

zero speed and at maximum speed. During each subsequentstart and stop, the starter dynamically adjusts its control toensure the motor's actual pe

Strany 26

NNOTEAAC Adaptive Acceleration Control will control the loadaccording to the programmed profile. Start current will varyaccording to the selected acce

Strany 27

010%20%30%40%50%TimeSpeed60%70%80%90%100%177HA510.1012431. Early deceleration2. Constant deceleration3. Late deceleration4. Stop time (Par. 1-10) TTab

Strany 28 - 4.11 Schematic Diagrams

The maximum available torque for jog is approximately 50%- 75% of motor full load torque (FLT) depending on themotor. Available jog torque in reverse

Strany 29 - 177HA426.11

AApplication Typical Start CurrentGeneral & WaterAgitator 4.0 x FLCCentrifugal pump 3.5 x FLCCompressor (Screw, unloaded) 3.0 x FLCCompressor (Rec

Strany 30

5.8 Installation with Main ContactorThe MCD 500 is installed with a main contactor (AC3 rated). Control voltage must be supplied from the input side

Strany 31 - 5.3.2 Current Ramp

5.9 Installation with Bypass ContactorThe MCD 500 is installed with a bypass contactor (AC1 rated). The bypass contactor is controlled by the MCD 500

Strany 32 - Voltage (% full voltage)

5.10 Emergency Run OperationIn normal operation the MCD 500 is controlled via a remote two wire signal (terminals 17, 18).Emergency Run is controlled

Strany 33 - 177HA511.10

5.11 Auxiliary Trip CircuitIn normal operation the MCD 500 is controlled via a remote two wire signal (terminals 17, 18).Input A (terminals 11, 16) i

Strany 34 - 5.7 Typical Start Currents

6.4.2 Programmable Screen (S2) 446.4.3 Average Current (S3) 446.4.4 Current Monitoring Screen (S4) 446.4.5 Frequency Monitoring Screen (S5) 446.4.6 Mo

Strany 35

5.12 Soft BrakingFor high inertia loads the MCD 500 can be configured for soft braking.In this application the MCD 500 is employed with forward run an

Strany 36 - 177HA522.10

NNOTEIf the MCD-500 trips on supply frequency (Par. 16-5Frequency) when the braking contactor KM2 opens, modifythe setting of Pars. 2-8 - 2-10.5.13 T

Strany 37 - 177HA523.10

NNOTEContactors KM2 and KM3 must be mechanically interlocked.Parameter settings:•Par. 3-3 Input A Function•Select Motor Set Select - assigns Input A f

Strany 38 - 5.10 Emergency Run Operation

6 Operation6.1 Operation and LCP6.1.1 Operating ModesIn Hand On mode:••To soft start the motor, press [HHAND ON] on theLCP•To stop the motor, press [

Strany 39 - 5.11 Auxiliary Trip Circuit

11Four-line display for status and programming details.2Display control buttons: SStatus: Return to the status displaysQuick Menu: Open the Quick Menu

Strany 40 - 5.12 Soft Braking

6.4 DisplaysThe LCP displays a wide range of performance informationabout the soft starter. Press the SSTATUS button to access thestatus display scree

Strany 41 - 5.13 Two Speed Motor

6.4.8 Date and Time (S8)The date/time screen shows the current system date andtime (24 hour format). For details on setting the date andtime, seeSet D

Strany 42

7 ProgrammingYou can access the programming menus at any time,including while the soft starter is running. All changes takeeffect immediately.7.1 Acce

Strany 43

7.2 Quick Menu7.2.1 Quick SetupQuick setup provides access to commonly used parameters, allowing the user to configure the MCD 500 as required for the

Strany 44 - 6.3 Local Control Buttons

7.2.2 Application SetupsThe application setups menu makes it easy to configure the MCD 500 for common applications. The MCD 500 selects theparameters

Strany 45

7.12 Restricted Parameters607.13 Protection Action617.14 Factory Parameters618 Tools628.1 Set Date and Time628.2 Load/Save Settings628.3 Reset Thermal

Strany 46 - 6.4.10 Performance Graphs

7.2.3 LoggingsThe Loggings menu allows the user to view performanceinformation in real-time graphs.••Current (%FLC)•Motor Temp (%)•Motor kW (%)•Motor

Strany 47

7.3.3 Parameter List11 Primary Mtr Set 4 Outputs7-11 Stop Time-21-1 Motor FLC 4-1 Relay A Function 7-12 Adaptv Ctrl Gain-21-2 Locked Rotor Time 4-2 Re

Strany 48 - 7.2.1 Quick Setup

7.4 Primary Motor SettingsNNOTEDefault settings are marked with .The parameters in Primary Motors Settings configure the softstarter to match the co

Strany 49 - 7.2.2 Application Setups

11-11 Stop TimeRange: Function:0 secs* [0:00 - 4:00(min:secs)]Sets the time for soft stopping the motorusing timed voltage ramp or AdaptiveControl

Strany 50 - 7.3.2 Parameter Shortcut

22-4 UndercurrentRange: Function:20%* [0% -100%]Sets the trip point for undercurrent protection,as a percentage of motor full load current. Set toa

Strany 51 - 7.3.3 Parameter List

33-2 Comms in RemoteOption: Function:Selects whether the starter will accept Startand Stop commands from the serialcommunication network when in Remo

Strany 52 - 7.4 Primary Motor Settings

7.7 Outputs44-1 Relay A FunctionOption: Function:Selects the function of Relay A (normally open).Off Relay A is not usedMain ContactorThe relay clos

Strany 53 - 7.5.2 Undercurrent

undercurrent or instantaneous overcurrent trip levels. Theflags can signal the situation to external equipment via oneof the programmable outputs. The

Strany 54 - 7.6 Inputs

55-4 Auto-Stop TimeRange: Function:1 min* [00:01 -24:00(hrs:min)]Sets the time for the soft starter to auto-stop, in 24 hour clock format.CAUTIONTh

Strany 55 - * [00:00 - 30:00

77-5 Initial Current-2Range: Function:350%* [100% -600% FLC]Sets the initial start current level for currentramp starting, as a percentage of motor

Strany 56 - 7.7.2 Relays B and C

1 Safety1.1 SafetyWhen reading this manual you will come across differentsymbols that require special attention. The symbols used arethe following:NNO

Strany 57 - 7.8 Start/Stop Timers

7.11 Display88-1 LanguageOption: Function:Selects which language the LCP will useto display messages and feedback.EnglishChinese (ЁϜ)Spanish (Españ

Strany 58 - 7.10 Secondary Motor Set

88-5 User Screen - Bottom RightOption: Function:Mains Frequency The average frequency measured on threephases.Motor kW The motor's running power

Strany 59

115-4 Current CalibrationRange: Function:&DOLEUDWLRQ &XUUHQWVKRZQRQ0&'GLVSOD\&XUUHQWPHDVXUHGE\H[WHUQDOGHYLFHH

Strany 60 - 7.11 Display

8 ToolsTo access Tools, open the Main Menu, scroll to Tools andpress OOK.8.1 Set Date and TimeTo set the date and time:1. Open the Tools Menu.2.Scrol

Strany 61 - 7.12 Restricted Parameters

TTo use the protection simulation:1. Open the Main Menu.2. Scroll to Protection Sim and press OOK.3.Use the Ⴃ and Ⴍ buttons to select the protectionyo

Strany 62 - * [100 - 2000

TTo open the Trip Log:1. Open the Alarm Logs.2. Scroll to Trip Log and press OOK.3.Use the Ⴃ and Ⴍ buttons to select a trip to view, and press OOK to

Strany 63 - 8.4 Protection Simulation

9 TroubleshootingWhen a protection condition is detected, the MCD 500 willwrite this to the event log and may also trip or issue awarning. The soft st

Strany 64 - 8.8.1 Trip Log

DDisplay Possible cause/Suggested solutionHeatsink Overtemp Check if cooling fans are operating. If mounted in an enclosure, check if ventilation is a

Strany 65 - 8.8.3 Counters

DDisplay Possible cause/Suggested solutionMotor Thermistor The motor thermistor input has been enabled and:-The resistance at the thermistor input has

Strany 66

9.2 General FaultsThis table describes situations where the soft starter does not operate as expected but does not trip or give a warning.SSymptom Pro

Strany 67

2 IntroductionThe MCD 500 is an advanced digital soft start solution for motors from 7 kW to 800 kW. MCD 500 soft starters provide acomplete range of

Strany 68

SSymptom Probable CauseAAC adaptive acceleration control, DC brakeand Jog functions not working-These features are only available with in-line install

Strany 69 - 9.2 General Faults

10 SpecificationsSupplyMains voltage (L1, L2, L3)MCD5-xxxx-T5 200 VAC - 525 VAC (s 10%)MCD5-xxxx-T7 380 VAC - 600 VAC (s 10%) (inside delta connection

Strany 70 - Symptom Probable Cause

Storage temperature - 25° C to + 60° COperating Altitude 0 - 1000 m, above 1000 m with deratingHumidity 5% to 95% Relative HumidityPollution degree Po

Strany 71

10.1.2 PC SoftwareMCD PC Software can be used in conjunction with a communications module to provide the following functionality fornetworks of up to

Strany 72 - 10.1.1 Communication Modules

11 Bus Bar Adjustment Procedure (MCD5-0360C - MCD5-1600C)NNOTEMany electronic components are sensitive to staticelectricity. Voltages so low that they

Strany 73 - 10.1.3 Finger Guard Kit

1. Remove all wiring and links from the soft starter before dismantling the unit.2. Remove the unit cover (4 screws).3. Unscrew the main plastic and f

Strany 74

NNOTEIf moving the input bars, the CTs must also be reconfigured.1. Label the CTs L1, L2 and L3 (L1 is leftmost whenworking from the front of the star

Strany 75

www.danfoss.com/drives *MG17K302*175R0549 MG17K302 Rev. 2010–09–03

Strany 76

2.1.2 Type CodeMCD 5-- - -Current rating0021 = 21 A, AC53b 3-30:3300037 = 37 A, AC53b 3-30:3300043 = 43 A, AC53b 3-30:3300053 = 53 A, AC53b 3-30:33000

Strany 77 - *MG17K302*

3 Installation3.1 Mechanical Installation1MCD5-0021B - MCD5-0245C: Allow 100 mm (3.94 inches) between soft starters.MCD5-0360C - MCD5-1600C: Allow 200