M
81331 Rev 01 Nov 2010
30
A
uto Tip-up Test Tip-up testing is used for testing power
components with voltage dependent dissipation
factor (e.g. generators) or in case a voltage
dependence is suspected and indicated by high
V
DF in Delta4000. The highest voltage level
used is set on main page and the voltage per
step is set on the settings page Voltage steps
can be set on the settings page
Frequency Sweep Frequency Sweep allows the user to perform a
series of tests over a frequency range. The
v
oltage level used is set on main page and the
v
oltage per step is set on the settings page. Note
that there are limitation of voltage levels at high
frequencies and low frequencies below 45 Hz
Manual
T
his mode allows continuous manual control of
output voltage.