Delta RMC101 Uživatelský manuál Strana 348

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 951
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 347
RMC100 and RMCWin User Manual
5-98
6. Fill in the fields in this dialog box as follows:
General:
Name
Type a valid module name for the RMC.
Description
Type a description.
Comm Format
Select one of the following formats:
Data - INT
Input and Output Data will be allocated. Only a
single connection originator (ControlLogix CPU)
can use this format for any given RMC.
Input Data - INT
Input Data only will be allocated. Up to four
connection originators can use this format
simultaneously.
Address/
Host Name
Enter the IP address or host name of the RMC.
The RMC must have its IP address set up to
match this address. See RMC Ethernet IP
Address Setup for details.
To use a host name, the DNS server must be
configured independently from the RMC. The
RMC has no built-in DNS support.
Connection Parameters:
Assembly
Instance
Data
Size
Size
Input
1
16-
bit
1 plus 10 per axis (11, 21, …,
81)
Output
2
16-
bit
1 plus 6 per axis (7, 13, …,
49)*
Configuration
4 8-bit
0 or 1
* If the "Input Data - INT" Comm Format is selected, the size for the Output will be unavailable.
The Assembly Instance must still be set to 2.
See Controlling the RMC over EtherNet/IP I/O for a description of the contents of the Input,
Output, and Configuration data areas.
Note: The Status Input and Output assembly options are not used by the RMC.
7. Click Next. The following dialog box will be displayed:
Zobrazit stránku 347
1 2 ... 343 344 345 346 347 348 349 350 351 352 353 ... 950 951

Komentáře k této Příručce

Žádné komentáře